First, check whether the fuel burner is OK, that is, whether the reset button of the burner program controller lights up with a red light (also called an alarm light). If the light does not light up, check whether the burner power supply is not input;

The power supply is normal and the alarm light is on. Press the reset button for 1 second and release the burner. The red light subsides but quickly turns red again. This is a problem with the flame detection system of the burner. The burner does not catch fire but the burner program controller An interference signal that a flame has been formed is received, which may be caused by light leakage from the combustion chamber, damaged photoelectric eye, short circuit of the photoelectric eye signal line, etc.;

Press the reset button for 1 second to release the burner fan action, but the electric spark does not appear when it should appear, and then the alarm is confirmed.