Facebook
Categories

Eacoon Completes Emission-Reduction Retrofit for Oil Refinery — Now Fully Operational

Eacoon Completed an Emission-Reduction Retrofit For an Oil Refinery Using Hydrogen-Rich Tail Gas With H2 up to 40%, Combustion Air Preheated Above 220°C, And Verified NOx emissions strictly under 40 mg/m³.
Oct 20th,2026 85 Views
“We put technology into action for our environmental mission, contributing great strength to a cleaner sky.” — Eacoon Group has successfully delivered an ultra-low emission combustion retrofit for an oil refinery facility. Utilizing hydrogen-rich process tail gas with hydrogen content reaching up to 40% and combustion air preheated to over 220°C, the system has achieved strict NOx emissions within 40 mg/m³, meeting and exceeding all environmental compliance standards.

1. Project Background: Decarbonization & Tail Gas Recovery in Oil Refining

In modern petrochemical and petroleum refining facilities, hydrogen-rich tail gas is often generated as an industrial byproduct. While possessing high calorific potential, this gas stream exhibits intense combustion speeds, elevated flame temperatures, and wide flammability limits. When combined with preheated combustion air exceeding 220°C, conventional burner systems face severe operational hazards, including premature flashback, combustion instability, and high thermal NOx formation.

To address these technical bottlenecks, Eacoon Group was commissioned to deliver an end-to-end combustion system retrofit. The engineering objective was clear: stably burn process byproduct tail gas containing up to 40% hydrogen, operate under continuous high-temperature preheated air conditions, and ensure flue gas NOx emissions remain strictly below 40 mg/m³ across normal operating loads.

Eacoon industrial burner and combustion air blower system for oil refinery emission reduction project
Figure 1: Eacoon heavy-duty industrial combustion air blower, preheated ducting, and automated gas control skid commissioned on site at the oil refinery.

2. Key Technical Innovations & Engineering Highlights

To safely handle high hydrogen concentrations and high preheated air temperatures simultaneously, Eacoon implemented a series of patented combustion control architectures:

Multi-Stage Fuel Injection & Staged Combustion

Hydrogen gas features a laminar burning velocity approximately five to seven times faster than natural gas. Eacoon's proprietary burner design divides the fuel gas feed into central and circumferential staging zones. By introducing fuel in controlled stoichiometric stages, peak localized flame temperatures are suppressed, fundamentally curtailing the thermal (Zeldovich) NOx formation mechanism.

Robust Stainless Steel Burner Architecture

High air preheat (>220°C) demands superior thermal stress resilience and expansion accommodation. As shown in the field equipment inspection below, the burner head is precision-fabricated from high-grade stainless steel with specialized cooling air channels, robust dual ignition probes, and continuous optical flame monitoring sensors to safeguard 24/7 continuous refinery operations.

Heavy-duty stainless steel hydrogen-rich tail gas burner head engineered by Eacoon
Figure 2: Custom heavy-duty stainless steel burner head with integrated flame monitoring.

3. Rigorous Field Testing & Emission Verification Data

Following comprehensive on-site commissioning, official flue gas emissions were measured using a calibrated, professional Testo 330LL-2 industrial flue gas analyzer (Serial Number: 03582613). All operational data confirmed stable, compliant performance under actual refinery production loads: Figure 3: On-site Testo 330LL-2 flue gas measurement screen verifying compliance.

Commissioning Parameter Measured Field Value Compliance Target / Benchmark Engineering Evaluation
Nitrogen Oxides (NOx) 33.1 mg/m³ (14.8 ppm NO) Strictly controlled < 40 mg/m³ Passed with significant compliance safety margin
Carbon Monoxide (CO) 1 ppm (1 mg/m³) < 100 ppm threshold Near-zero unburned emissions; complete combustion
Flue Gas Oxygen (O₂) 3.9% 3.0% – 4.5% target window Optimized air-to-fuel ratio minimizing thermal heat loss
Gross Thermal Efficiency 82.9% > 80% industrial target Delivers direct energy savings for the refinery utility plant
Flue Gas Exhaust Temp 185.1 °C Standard operational range Thermal profile safely above acid dew point (57.6°C)
Combustion Air Temperature > 220 °C High-temperature preheat Fully recovers industrial waste heat without flame instability
Hydrogen Concentration Up to 40% H₂ Byproduct tail gas Stable burner flame envelope without flashback or pulsation

Project Achievement Summary

  • Full Operational Readiness: The refinery system has successfully passed all commissioning tests and is in full commercial operation.
  • Ultra-Low NOx Guaranteed: Real-time flue gas NOx consistently maintained at 33.1 mg/m³, meeting stringent national environmental regulations.
  • Environmental Impact: Replaces external utility fuels with internal byproduct gas, cutting operational energy costs and atmospheric carbon emissions simultaneously.

4. Frequently Asked Questions (FAQ)

Q1: Can Eacoon burners handle fluctuating hydrogen concentrations in tail gas?

Yes. Eacoon's intelligent combustion control system incorporates real-time fuel gas Wobbe Index compensation and dynamic air-fuel ratio modulation, safely accommodating hydrogen content fluctuations from 5% to 40% (and up to 100% with dedicated hydrogen-firing models).

Q2: How does the system achieve <40 mg/m³ NOx with 220°C hot air without external FGR?

By combining aerodynamic internal flue gas recirculation (IFGR), high-velocity micro-orifice fuel gas staging, and flame temperature peak flattening, the burner keeps thermal NOx formation minimal even with high-temperature combustion air.

Q3: What industries can benefit from this tail gas emission retrofit?

This solution is widely applicable to petroleum refineries, chemical plants, coking facilities, metallurgical plants, and any industrial facility generating hydrogen-rich, CO-rich, or low-calorific process tail gases.

Planning an Emission-Reduction or Tail Gas Combustion Project?

Connect with Eacoon's senior combustion engineering specialists to evaluate your plant's fuel gas composition, calculate efficiency gains, and design customized ultra-low NOx solutions.

Visit Eacoon Official Website