Facebook
Categories

Twelve TJ0050 Burners Replace an Obsolete Line at a Mexican Bentonite Calciner

A bentonite calciner in Mexico has replaced twelve burners that are no longer manufactured with Eacoon TJ0050 units at 500,000 Btu/h and a 10:1 turndown; all thirteen burners now report normal on the HMI.
Nov 13th,2026 8 Views

Project record · Mexico · Bentonite calcination · In service since 2025

A bentonite calciner in Mexico has replaced twelve burners that are no longer manufactured, and the line is running. The original TJ050HAT-NF units were obsolete and the plant’s own atmospheric burner had already stopped. The three modules of four now carry Eacoon TJ0050 burners at 500,000 Btu/h with a 10:1 turndown, a DN65 gas train, a 4,500 m³/h variable-speed air supply, twelve local control boxes, one Siemens PLC cabinet and a GT-20 atmospheric burner as No. 13. On the HMI today, all thirteen report normal.

Item Detail
Project data Bentonite calciner burner replacement, Mexico
Application Bentonite calcination; three burner modules of four
Burners 12 × Eacoon TJ0050; 1 × GT-20 atmospheric burner at the end of the line
Rating per burner 500,000 Btu/h (146.5 kW); 10:1 turndown to 50,000 Btu/h (13 kW)
Installed capacity 1,758 kW (12 × 146.5 kW)
Combustor AISI 310 alloy, 950 °C chamber limit; 210 mm wall and flame tube
Combustion air 4,500 m³/h at 6–8 kPa, 30 kW, VFD; no induced-draft fan
Connections 1-inch NPT fuel, 2½-inch NPT air; DN65 main gas and air headers
Temperature zoning Six zones of two burners; three burner modules of four
Control Siemens PLC + 10-inch HMI; 6 × DC1040 at 500 °C, 800 °C alarm
Status In service; all 13 report normal on the HMI

Project background

The Mexican calciner dries and calcines bentonite. Product leaves at around 350 °C and the calcination zone runs between 700 and 900 °C. Each burner sits in a 210 mm wall, so the flame tube cannot be lengthened to buy mixing time — whatever happens has to happen inside that depth.

The installed TJ050HAT-NF is out of production and spares are gone, but the harder requirement came from the plant’s temperature logic: the vapour outlet must hold a band, because too cold condenses in the downstream purification and too hot damages it. A PID loop trims dilution air through a servo valve to hold that band, and its low-temperature alarm must start a burner on its own. The replacement had to reproduce the heat input, the ignition sequence of twelve burners and a safety burner that runs independently of them.

The difficulty was not the 146.5 kW rating. The same device is a mechanical interface, an ignition programme and a temperature-safety element at once, and each of the three is specified by a different document.

What Eacoon delivered

The order covered the complete firing line rather than the burners alone: twelve TJ0050 burners with 1-inch gas and 2½-inch air connections, stainless flexible connectors, twelve ratio regulators with manual trim valves and solenoids, twelve air butterfly valves on Kromschröder IC 20-07W2T actuators, a DN65 main gas train with filter, volume corrector, overpressure shut-off, regulator and double safety solenoid, a DN65 air header, twelve burner control boxes, one 800 × 500 × 2000 mm PLC cabinet and the GT-20 safety burner with its own package.

Eacoon TJ0050 burner in service at a Mexican bentonite calciner: main gas train, ratio regulator, solenoid and flame scanner

TJ0050 burner in service: gas train, ratio regulator, solenoid and flame scanner on the burner body. Photo: Eacoon.

Three decisions carried the project:

  • Ratio control at the burner, not the module. With one VFD blower feeding twelve burners across three modules, a module-level valve would leave each to find its own mixture; a regulator on every burner keeps the pairs in a zone identical.
  • One control box per burner. Controller, ignition transformer and terminals sit in a 400 × 300 × 250 mm enclosure beside each. A flame failure takes out one box and one burner, not a module, and the fault is visible at the equipment.
  • A gas train built, not assembled on site. The DN65 main, branch manifolds and twelve control boxes are prefabricated and wired in the workshop; site work is bolting flanges and pulling customer cable.

In service: what the panel and the HMI show

The system is running. The cabinet carries the six zone controllers and the 800 °C alarm, with reset, mute and stop-running on the door. The HMI puts the whole calciner on one screen: No. 1 to No. 13 with power status, the six zone temperatures and their average, main valve position, high and low gas pressure switches, and the combustion-air fan speed.

HMI main control screen showing burner No. 1 to No. 13, six zone temperatures, main valve position and combustion air fan speed

HMI main control screen: thirteen burners, six zone temperatures, main valve and fan speed on one page. Photo: Eacoon.

On the day it was photographed the six zones ran between roughly 280 and 350 °C against the 500 °C ceiling, with the fan at 29 Hz of its 30 Hz setpoint — well below the limit, where a calciner normally sits once the dilution-air loop is in charge. The status line reads that all burners run normally.

Six Honeywell DC1040 zone controllers set to 500 degrees C with an 800 degrees C high-temperature alarm instrument

Six zone controllers, Zone A to F at 500 °C, with the 800 °C alarm instrument at the top right. Photo: Eacoon.

Twenty years of burner replacement behind the project

Eacoon has worked in industrial combustion for more than twenty years, with in-house R&D, core patents and participation in drafting industry group standards. Much of that work is replacement rather than new-build: matching equipment to an opening that already exists, a wall thickness that cannot change and a control philosophy the plant already runs.

  • 12 + 1 burners — twelve main units and one atmospheric safety burner
  • 10:1 turndown, 500,000 Btu/h down to 50,000 Btu/h
  • 6 zones of two burners, inside three gas and air modules

The reference base covers metallurgy, heat treatment, non-ferrous melting, building materials and solid-waste incineration, in China and on export projects. Recent records include a 60-burner low-NOx retrofit in Lanzhou, a burner system for a waste-to-energy plant in Palembang and an emission retrofit for an oil refinery on hydrogen-rich tail gas.

Frequently asked questions

Can an obsolete burner be replaced without rebuilding the furnace wall?

Yes, if the new one is dimensioned to the existing opening. Here the mounting dimension measured B = 124 mm, the first proposal was drawn at 114 mm, and the unit was re-dimensioned before manufacture; the 210 mm wall was left untouched.

What does 10:1 turndown mean for a calciner?

One burner covers 500,000 Btu/h down to 50,000 Btu/h, and 10,000 Btu/h in fixed-air mode, without cycling at low load. That keeps the firing rate stable while the dilution-air loop trims the vapour band.

Why keep the atmospheric burner outside the main PLC?

Because it starts on the low-temperature alarm of the vapour-outlet loop, which must work when the twelve main burners are off and the PLC is in a different state. It carries its own solenoids, ignition transformer, controller and regulator.

What is needed to quote a drop-in replacement burner?

The original drawing and mounting dimension, the rated duty in your units, the wall thickness, fuel data, supply voltage and frequency, and the control philosophy the plant runs. Usually that is enough without a site visit.

Replacing a line that is out of production?

Send the original drawing, the mounting dimension, the rated duty and the wall thickness — we will come back with a drop-in configuration and an ignition and safety concept.

Tel +86 139 2888 4373  ·  Sales@eacoon-burner.com